Elcom International

Individual Metered & Switched

ES3-B24V

Specifications

Input

Nominal Voltage
415 VAC
Rated Voltage
380-440 VAC
Frequency
50 Hz / 60 Hz
Input Plug
3Φ, 30A/32A, IEC 60309 (3P+N+E), 440VAC, 6hr, IP44
Cord Length
3 meters, 45° Angled
Input Current
32 A
Power Rating
21 kVA at 380 VAC, 24 kVA at 440 VAC

Output

Nominal Voltage
230 VAC / phase
Rated Voltage
200-250 VAC / phase
Frequency
50 Hz / 60 Hz
Receptacles Configuration
ELGO Combo Max 5-in-1, 24 Nos (C13 / C15 / C15A / C19 / C21)
Over Current Protection
Six (6) × 16A Hydraulic Magnetic Circuit Breakers, 10kAIC

Features

Input and Outlet MonitoringVoltage (V), Current (I), Apparent Energy (kVAh), Reactive Energy (kVARh), Active Energy (kWh), Power factor, Apparent Power (kVA), Reactive Power (kVAR), Active Power (kW), Frequency (Hz)
Outlet Metering & SwitchingProvides independent outlet-level monitoring of electrical parameters for precise load analysis and efficient power management. Supports individual outlet ON/OFF switching through Web, SNMP, CLI, and API interfaces, with secure access and local/manual override for reliable and flexible operation. Power Measurements Compliant with ANSI C12.1 and IEC 62053- 21 conforms to CLASS 1 metering accuracy
User Interface1.77-inch TFT colour LCD for local status and measurement display. A secure and responsive web-based user interface provides real-time power and environmental monitoring, alarm notifications, and access to historical logs from any standard web browser. Seamless integration with DCIM systems is supported via SNMP and Modbus TCP protocols
Protocol SupportHTTP(s), SNMP v1, v2c, v3, MODBUS TCP, SFTP, DHCP, IPV4, IPV6 Support, Telnet (CLI), NTP, SMTP, SSH, Redfish API, Syslog, LDAP, RADIUS, TACACS+, TLS 1.3
NetworkingPrimary Gigabit Ethernet (10/100/1000) port with secondary redundant 10/100 Ethernet port
CascadingSupport cascading of 16 iPDUs/controllers for centralized monitoring and management via a single network connection. Cascading reduces network port usage and simplifies installation while ensuring reliable data communication between master and slave units
Threshold SettingUsers can configure threshold limits for low load, near-overload, and overload conditions for input current at phase level. Thresholds can also be defined for lower and upper limits of temperature and humidity sensors. Visual indication is provided via front-panel LEDs, along with an optional audible buzzer alarm.
Notification & AlertsComprehensive alerts delivered over SMTP (email) and SNMP traps. Optional local audible/visual alarms ensure immediate awareness. Real-time detection of circuit breaker trips with local alarms and remote notifications on current threshold exceedance Configurable notifications for temperature/humidity exceedance, maintaining optimal rack conditions. Supports external sensors with warning/critical levels via SNMP/SMTP. Instant alerts for door open/close, smoke detection, and water sensor via SNMP traps or email. Integrates with DCIM for automated responses
Firmware UpgradeSupports remote firmware upgrades over HTTPS with dual LAN ports for zero-downtime access. Local USB upgrades enable offline deployment in secure environments
Compatible SensorsTemperature, Humidity, Dew Point, Air Flow, Water Sensor, Smoke Detection and Door Position
Data loggingEmbedded non-volatile memory logs key metrics including voltage, current, power (kW/VA), energy (kWh), power factor, frequency, and events with timestamps. Supports data export via CSV for analysis; retention up to 365 days or 1000+ records.
Outlet FeaturesElgo Series outlet/Receptacles combination of C13/C15/C15A/C19/C21 as per IEC 61984/ IEC 60320 and CE, TUV, UL, CSA certified. E-lock provision for standard power cord locking. Alternate Phase Receptacles per branch. (Black – Grey – White)

Environmental Requirements

Maximum Operating Temperature
60 °C
Relative Humidity
95 % RH non-condensing

Conformance

Certification
UL, cULus
Compliance
CE
Environmental
RoHS
Standards
IEC 62368-1

Mechanical

Dimensions (H × W × D)
Weight
Toolless Mounting — Centre to Centre
Mounting Configuration
Zero U / Vertical
Shipping Dimensions
Shipping Weight
Material
CRCA
Colour
Blue

Mechanical & electrical drawings

For the mechanical and electrical diagram, please contact us at mail@elcom-in.com.